Growatt — the world's #1 residential solar inverter brand by Wood Mackenzie. The MID 36KTL3-X2 is a three-phase commercial string inverter. Designed for C&I rooftops in JAFZA, Riyadh industrial zones, and warehouse installations across the Gulf.
- Max. recommended PV power (for module STC): 54000W
- Max. DC voltage: 1100V
- Start voltage: 200V
In stock
Growatt MID 36KTL3-X2 features
About the Growatt MID 36KTL3-X2
Growatt — the world's #1 residential solar inverter brand by Wood Mackenzie. The MID 36KTL3-X2 is a three-phase commercial string inverter. Designed for C&I rooftops in JAFZA, Riyadh industrial zones, and warehouse installations across the Gulf. Key features: 1100V DC architecture, IP66, smart string monitoring. 5- to 5-year warranty. Available across the Middle East, Europe, and Africa via Growatt MJS Solutions, the authorised distributor based in Dubai. Remote monitoring via the ShinePhone app and ShineServer cloud — view performance from anywhere, configure alerts, and manage multiple sites.
Specifications last updated 23 July 2026
Growatt MID 36KTL3-X2 full specifications
Electrical
| Max. recommended PV power (for module STC) | 54000W |
|---|---|
| Max. DC voltage | 1100V |
| Start voltage | 200V |
| Normal voltage | 600V |
| MPPT voltage range | 200-1000V |
| No. of MPP trackers | 3 |
| No. of PV strings per MPP tracker | 2 |
| Max. input current per MPP tracker | 32A |
| Max. short-circuit current per MPP tracker | 40A |
| AC nominal power | 36000W |
| Max. AC apparent power | 40000VA |
| Nominal AC voltage (range) | 220V/380V, 230V/400V (340-440V) |
| AC grid frequency (range) | 50/60 Hz (45-55Hz/55-65 Hz) |
| Max. output current | 60.6A |
| Adjustable power factor | 0.8leading...0.8lagging |
| THDi | <3% |
| AC grid connection type | 3W+N+PE |
| Max. efficiency | 98.8% |
| European efficiency | 98.5% |
| MPPT efficiency | 99.9% |
| DC reverse polarity protection | Yes |
| DC Switch | Yes |
| AC/DC surge protection | Type II / Type II |
| Insulation resistance monitoring | Yes |
| AC short-circuit protection | Yes |
| Ground fault monitoring | Yes |
| Grid monitoring | Yes |
| Anti-islanding protection | Yes |
| Residual-current monitoring unit | Yes |
| String monitoring | Yes |
| AFCI protection | Optional |
| Self-consumption (night) | < 1W |
Mechanical
| Dimensions (W / H / D) | 528/415/225mm / 580/435/230mm / 580/435/230mm / 580/435/230mm / 580/435/230mm |
|---|---|
| Weight | 34kg |
| Operating temperature range | -25°C...+60°C |
| Nighttime power consumption | <1W |
| Topology | Transformerless |
| Cooling | Smart air cooling |
| Protection degree | IP66 |
| Relative humidity | 0-100% |
| Altitude | 4000m |
| DC connection | H4/MC4(Optional) |
| AC connection | Cable gland+OT terminal |
| Display | OLED+LED+WIFI+APP |
| Interfaces: RS485/USB/WIFI/GPRS/RSF/LAN | Yes/Yes/Optional/Optional/Optional/Optional |
Related Products

MID 33KTL3-X2
- Max. recommended PV power (for module STC):49500W
- Max. DC voltage:1100V

MID 40KTL3-X2
- Max. recommended PV power (for module STC):60000W
- Max. DC voltage:1100V

MID 30KTL3-X2
- Max. recommended PV power (for module STC):45000W
- Max. DC voltage:1100V

MID 50KTL3-X2
- Max. recommended PV power (for module STC):75000W
- Max. DC voltage:1100V
Related Articles
Best Growatt Commercial Inverter in 2026 — MID, MAX & WIT for 50–500 kW
Selecting a Growatt commercial inverter for a 50 to 500 kW rooftop or ground-mount? We compare MID, MAX, and WIT series with ROI math for MENA C&I installs.
Read: Best Growatt Commercial Inverter in 2026 — MID, MAX & WIT for 50–500 kW →Growatt vs Deye Inverters — Full 2026 Comparison for UAE and KSA Buyers
Detailed growatt vs deye inverters comparison: efficiency, battery flexibility, monitoring (ShinePhone vs SolarMan), warranty, regional support across the Gulf.
Read: Growatt vs Deye Inverters — Full 2026 Comparison for UAE and KSA Buyers →Growatt Time of Use Solar Net Metering — Programming SPH for DEWA and SEC TOU Tariffs
Growatt time of use solar net metering: program SPH inverters via ShinePhone for DEWA Shams Dubai TOU and SEC peak/off-peak tariffs. Sample schedules and AED savings.
Read: Growatt Time of Use Solar Net Metering — Programming SPH for DEWA and SEC TOU Tariffs →